FLT93L FlexSwitch® Flow Switch
Flow Switch SummaryThe FLT93L inline type FlexSwitch for flow and temperature monitoring
represents the first true technological breakthrough in thermal
technology in over a decade. FCI is the only thermal manufacturer
providing temperature compensation to ensure set point accuracy for
process temperatures that vary up to ± 100° F. The FLT93L is easily
field-configured or factory preset, providing unparalleled flexibility,
accuracy and stability for all multiple process sensing and switching
requirements.
For an operational demonstration of FCI's FLT93 FlexSwitch Series,
please follow this
link. |
Applications |
Chemical additive verification |
Coolant and lubrication seal leakage |
Lube oil flow detection |
Air flow purge monitoring |
Seal water flow detection |
Spray nozzle monitoring |
SpecificationsFor Flow Service - Setpoint Range:
Water-based Liquids:
0.015 to 50 cc/sec [0.0009 to 3 lps]
Hydrocarbon-based Liquids:
0.033 to 110 cc/sec [0.002 to 6.6 lps]
Air/Gas:
0.6 to 20,000 cc/sec [0.036 to 1198 lps]
Accuracy: (whichever reading is higher)
Liquids: ± 0.5% reading or ± 0.04 fps [± 0.012 mps]
Gases: ± 0.5% reading or ± 2 sfps [± 0.06 nmps]
For Temperature Service:
Accuracy: ± 2° F [±1° C]
Repeatability: ± 1° F [± 0.6° C]
Response Time: As low as 0.5 seconds
Enclosure: Powder coated aluminum enclosure is rated for hazardous
location use Groups B, C, D, E, F and G, CENELEC EEx d IIC and resists
the effects of weather and corrosion per NEMA/CSA Type 4X (equivalent to
IP66). Stainless steel is available as an option.
Agency Approvals: FM, CSA, CENELEC, ATEX, CE Mark, T4 Rated (System
Approval) and CRN.
Flow ElementMaterials of Construction: All-welded 316L stainless steel for all
wetted surfaces. Hastelloy C is available as an option.
Process Connection:
Standard: 1 inch male NPT or 0.75 inch female NPT at tee inlet and
outlet
Optional: Flanges
Inline Tee Length: 3.375 inch [86 mm]
Operating Temperature:
Standard: -4° to +350° F [-20° to +177° C]
Optional: -100° to +500° F [-73° to +260° C]
Operating Pressure: To 3500 psig [240 bar(g)] |
Control CircuitOperating Temperature: -40° to +140° F [-40° to +60° C]
Input Power: Field selectable 115 ± 15 Vac or 230 ± 30 Vac, 50/60 Hz; 21
to 28 Vdc or 18 to 26 Vac; 7 watts maximum.
Relay Contacts: Field configurable dual SPDT or single DPDT rated 6 amps
at 115 Vac, 240 Vac or
24 Vdc. Hermetically sealed relays are available as an option.
Output Signal: Analog DC voltage related to flow or level/interface
signal and proportional to temperature.
Electrical Connection: 1 inch female NPT
Remote Configuration: Available as an option with customer specified
interconnecting cable length. |
Optional N.I.S.T. Flow Calibration ServicesFactory N.I.S.T. calibration in air or water is available as an option
for customer specified setpoint(s) or a flow curve based on the media
ranges specified above |
|