FS2000H NuTec® 2 Wire Thermal Flow Switch
Flow Switch Summary
The FS2000H Flow Switch delivers a combination of the highest flow
range, accuracy and response time available with any thermal dispersion
switch. It is equally well suited for water, liquid, slurries, air, and
gases. The switch set point is fully field settable. Its unique "flat
face" sensor is designed to be mounted flush to the inner pipe surface
or can be extended into the media.
FS2000H can be used in clean or dirty media and is unaffected by
entrained bubbles or particulates. its no moving parts technology
ensures years of maintenance-free, non-clogging performance and creates
no pressure drop in the system. FS2000H temperature compensation, not
found in lesser switches, ensures highly repeatable switching in actual
field conditions.
Input power can be 24 Vac or Vdc, 100/240 Vac, or loop power where
instrument works off common 4-20 mA current loop. Signal for alarm or
limit trips can be 6A, SPDT relay or transistor output. Rugged NEMA 4X
[IP66] rated enclosure and 316L SS all-welded, sensor element delivers
durable long life.
|
Applications |
High flow alarm |
High viscosity flow monitoring |
Pump protection |
Chemical injection |
Seal leak detection |
HVAC monitoring |
Lubricant monitoring |
Relief valve flow detection |
Clean and purge lines |
Adhesive flow detection |
Fill drain control |
Gas with entrained particles |
SpecificationsSetpoint Range:
Water:
0.1 to 10 fps [0.03 to 3 mps]
Ethylene Glycol:
0.1 to 15 fps [0.03 to 4.6 mps]
Hydrocarbon-based Liquids:
0.2 to 20 fps [0.06 to 6 mps]
Air/Gas:
0.25 to 750 sfps [0.08 to 230 smps]
Repeatability: ± 1% of range
Response Time:
Water:
0.5 to 3 Seconds
Ethylene Glycol:
0.5 to 7 Seconds
Hydrocarbon-based Liquids:
0.5 to 6 Seconds
Air/Gas:
1 to 5 Seconds
Enclosure:
Aluminum NEMA Type 4X[IP66] rated for hazardous locations Groups B, C,
D, E, F, G and EEx d IIC
Agency Approvals: FM, CSA, CRN, CE Mark and ATEX (pending). |
Flow Element
Materials of Construction: All Welded 316L
Process Connection: 1” NPT, or 1” Compression Fitting
Insertion Length: Optimum Location Flush with I.D. of Pipe
Available in Fixed 2 inch and 6 inch with Compression Fitting
Operating Temperature: -40° to +250° F [-40° to +121° C]
Operating Pressure: 0 to 500 psig [35 bar(g)]
Control CircuitOperating Temperature: T6 Rated 0° to
+140° F [-18° to +60° C]
Input Power: 24 Vac or Vdc at 3 watts, 100/240 Vac at 3 Watts or Loop
Power 4 to 2 mA at 225 to 30VDC
Signal Output:
DC amd AC Power: SPDT 6 AMP Relay Resistive Max 240
Vac, Minimum 10Vdc at 20 mA, Transistor (FET) Output 250 mA Max on
Alarm, Field Selectable Transition for Flow or No Flow
Loop Power: 2 Step Output, Field Selectable Transition Alarm at 14
mA to 18 mA or 18 mA to 14 mA. Limited Flow Range Available with Loop
Power. Contact FCI for Flow Range.
Electrical Connection:
For 304/305 stainless steel: 0.5 inch female NPT.
For 316L stainless steel: 0.75 inch female NPT |
Optional N.I.S.T. Flow Calibration ServicesFactory N.I.S.T. calibration in air or water is available as an option
for customer specified setpoint(s) or a flow curve based on the media
ranges specified above |
|