Level Switch SummaryThe FLT93B BASIC insertion type
FlexSwitch for level and temperature monitoring represents the first
true technological breakthrough in thermal technology in over a decade.
FCI is the only thermal manufacturer providing temperature compensation
to ensure set point accuracy for process temperatures that vary up to ±
100° F. The FLT93B is easily field-configured, providing unparalleled
flexibility, accuracy and stability for all multiple process sensing and
switching requirements.
The FLT93B BASIC level switch is available with all of the below listed
standard features for a very attractive price and with quick delivery as
soon as 2 business days ARO.
For an operational demonstration of FCI's FLT93 FlexSwitch Series,
please follow this link. |
| |
Applications |
|
Interface and sump level detection |
|
Interface/level detection in settling vessels |
|
Interface/sump level detection in separation vessels |
|
Foam or sediment level control |
|
Agitation detection |
|
Liquid/resin interface detection |
SpecificationsFor Level/Interface Service:
Accuracy: ± 0.25 inch [± 6.4 mm]
Repeatability: ± 0.125 inch [± 3.2 mm]
For Temperature Service:
Accuracy: ± 2° F [±1° C]
Repeatability: ± 1° F [± 0.6° C]
Response Time: As low as 3 seconds.
Enclosure: Powder coated aluminum enclosure is rated for
hazardous location use Groups B, C, D, E, F and G, CENELEC EEx d IIC and
resists the effects of weather and corrosion per NEMA/CSA Type 4X
(equivalent to IP66). Stainless steel is available as an option.
Agency Approvals: FM, CSA, CENELEC, ATEX with CE Mark.
|
Flow Element
Materials of Construction: All welded 316L stainless steel for
all wetted surfaces.
Process Connection: 0.75 inch male NPT
Insertion Length:
1.2 inch [30 mm]
2 inches [51 mm]
4 inches [102 mm]
Operating Temperature: -40° to +350° F [-40° to +177° C]
Operating Pressure: To 3500 psig [240 bar(g)]
Control CircuitOperation Temperature: -4° to +140° F
[-20° to +60° C]
Input Power: Field selectable 115 ± 15 Vac or 230 ± 30 Vac (50/60
Hz); 21 to 28 Vdc or 18 to 26 Vac; 7 watts maximum.
Relay Contacts: Field configurable dual SPDT or single DPDT rated
6 amps at 115 Vac, 240 Vac or 24 Vdc.
Output Signal: Analog DC voltage related to flow or
level/interface signal and proportional to temperature.
Electrical Connection: 1 inch female NPT
|
Optional N.I.S.T. Flow Calibration ServicesFactory N.I.S.T. calibration in air or water is available as an option
for customer specified setpoint(s) or a flow curve based on the media
ranges specified above |