Specifications
For Flow Service
- Setpoint Range:
- Water-based Liquids: 0.01 to 7.0 fps [0.003 to 2,1 mps]
Hydrocarbon-based Liquids: 0.01 to 5.0 fps [0.003 to 1,5 mps]
Air/Gas: 0.25 to 120 sfps [0.08 to 37 smps]*
- *at standard conditions of 70° F [21.1° C] and 14.7 psia [1.013 bar(g)]
Accuracy (flow): ±2% of setpoint
Repeatability (flow): ±0.5% rdg
For Temperature Service:
- Accuracy: ±2°F [±1°C]
Repeatability: ±1°F [±0.6°C]
- Compliances and Agency Approvals: FM, FMc, ATEX/UKEX, IECEx, CE Mark. (Pending NEPSI, EAC/TR CU, INMETRO, EQM/UCAS, KCsEx, FMc with CRN.)
|
|
- Division Scheme, US (NEC 500) and Canada (CE Code Annex J18)
Class I, Div. 1 GPS B,C,D T6
Class I, Div. 2 GPS A,B,C,D T4A
Class II/III, Div. 1 GPS E,F,G T6
Class II/III, Div. 2 GPS E,F,G T4A
Type 4X, IP66/67
Ta= -40°C to 65°C
Zone Scheme, US (NEC 505) and Canada (CE Code Section18)
Class I, Zone 1, AEx db IIC T6...T1 Gb
Zone 21 AEx tb IIIC T85°C...T450°C Db
Type 4X; IP66/67; Ta= -40°C to 65°C
(Note: Standard instrument is tagged with Division scheme above. Alternate tagging with Zone scheme avaiable on special request. Contact FCI)
|
|
|
- II2G Ex db IIC T6…T1 Gb
II2D Ex tb IIIC T85°C…T450°C Db
IP66/67; Ta= -40°C to 65°C
|
|
|
- Ex db IIC T6…T1 Gb
Ex tb IIIC T85°C…T450°C Db
IP66/67; Ta= -40°C to +65°C
|
- IEC 61508: SIL 1 Compliant
- Optional N.I.S.T. Flow Calibration Services
- Factory N.I.S.T. calibration in air or water is available as an option for customer specified setpoint(s) or a flow curve based on the media ranges specified above.
- Flow Element
- Materials of Construction: Standard: All welded 316L stainless steel for all wetted surfaces. Optional Hastelloy-C. Monel or Titanium availble optionally with Model FLT201.
- Process Connection: Fixed NPT(M), Compression fitting, Flanged, Packing Gland
- Insertion Length: (Models FLT200, FLT201)
- Standard: 1.2" [30 mm], 2" [51 mm], 4" 102 mm]; 6" [152 mm]
Optional: Customer specified up to 99.9 inches [2515 mm]
- Operating Temperature: (process fluid)
- Standard: -40° to +250° F [-40° to +121° C] (with H-type sensor)
- -40° to +350° F [-40° to +177° C] (with S-type and FP-type sensors)
- Optional: -100° to +500° F [-73° to +260° C] (with S-type and FP-type sensors)
Optional: -100° to +850° F [-73° to +454° C] (Model FLT201 with S-type sensor only)
- Operating Pressure: Up to 3500 psig [241 bar(g)] depending process connection type and temperature. (Consult FLT200 Series brochure specifications for more detail.)
Transmitter/Electronics
- Operating Temperature: -40° to +149° F [-40° to +65° C]
- (Optional LCD readout -4°F [-20°C]. Instrument will continue to operate normally, but display itself may become unreadable below this temperature.)
- Input Power:
- Model FLT200: 24 Vdc, ±10% (6W max)
Model FLT201: 10 - 30Vdc (6W max) or 85 - 265 Vac (10W max)
- Relay Contacts:
- Model FLT200: Single SPDT Relay, 10A. (resistive load at 240Vac, 24Vdc)
Model FLT201:
Standard: Dual SPDT Relays or single DPDT, 10A. (resistive load at 240Vac/24Vdc.
Optional: Dual Hermetically-sealed Relays, (0.25A@230Vac, 2A@28Vdc)
Optional: 4-20mA Monitoring Analog Output. (Isolated and selectable for NAMUR NE43 fault guidelines)
- Display/Readout (Optional): Color, touchscreen LCD, backlighted. 1.54" [39 mm] diagonal, 57600 pixel. Perform all user set-ups via touchscreen. Display mode continuously shows flow or level state in comparison to trip point in both digital values and bargraph. Alarm condition (tripped relay) changes status indicator from steady-state to flashing red. Also displays diagnostics and service codes in the event of a fault condition.
Standard: NEMA 4X, IP66/67 rated low copper content aluminum, with dual conduit ports threaded as 1/2" NPT or M20x1.5; polyester powder coated.
Optional: Same as above in 316L Stainless steel, non-painted
Remote: Optionally available with Models FLT201 and FLT201L. Transmitter/Electronics are remoteable from the flow element up to 1000' [305 m]. Compatible remote cable, with jacketing of PVC, Telfon, or Armored, is also available.